Perhitungan Rerating Motor Induksi Akibat Tegangan Tidak Seimbang Dengan Metode William
Abstract
To calculate the rerating three-phase induction motor output due to supply voltage three-phase unbalanced done using the method of William. Unbalanced three-phase voltage obtained by simulation. Simulation is used Monte Carlo simulations to present three-phase induction motor condition with input voltages to the stator is unbalanced using the software MATLAB 7.
The results of calculations show the influence of unbalanced input voltage by a factor of 0.76% voltage imbalance – 8.41% of a three-phase induction motor rating can be seen in the form of a decrease in the power rating of three-phase induction motor 10 hp to 9.45 – 4.03 hp.
Keywords: rerating, Monte Carlo simulation, Method of William
Full Text:
PDFReferences
C S Indulkar, Monte Carlo Analysis of a Three-phase Induction Motor for Unbalanced Voltage Supply , IE (I) Journal-EL ,March 2007, vol 87
Kanwarjit Singh Sandhu , Vineet Chaudhary , Steady State Modelling of Induction Motor Operating With Unbalanced Supply System, Wseas Transactions on Circuits And Systems, February 2009, Vol 8
P Pillay, P Hofmann , M Manyage, Derating of Induction Motors Operating with a Combination of Unbalanced Voltages and Over or Undervoltages, IEEE Transactions on Energy Conversion, vol 17, December 2002, pp 485-491.
Texbooks:
BL Theraja, AK Theraja,), Text book of Electrical Technology Revised Edition, S Chand Company, New Delhi, 2002 : pages
C.F,Wagner and RD Evans, Symmetrical Components , RE Krieger Publication , Florida,1933
Refbacks
- There are currently no refbacks.
FAKULTAS SAINS DAN TEKNOLOGI
UIN SUSKA RIAU
Kampus Raja Ali Haji
Gedung Fakultas Sains & Teknologi UIN Suska Riau
Jl.H.R.Soebrantas No.155 KM 18 Simpang Baru Panam, Pekanbaru 28293
Email: sntiki@uin-suska.ac.id