ANALISIS KINERJA SISTEM KELISTRIKAN UNIVERSITAS LANCANG KUNING
Abstract
To distribute the electrical power needs of electricity producers to consumers required a distribution network and substations. Based on General Requirements for Electrical Installations ( PUIL ) 2000 and Standard State Electricity Company ( SPLN ), the system can be said to be effective if the voltage drop does not exceed 5 % of the nominal voltage and power loss does not exceed 10 % of the total power supplied The electrical system at the University of Lancang Kuning need to pay attention to large cross-section conductor and conductor prisoners are used to minimize power loss and voltage drop. The reliability of the electrical power distribution system is determined by efforts to minimize power loss and voltage drop occurs in the electrical system. Power loss and voltage drop affects the power distribution capabilities, both of which result from pengahantar channel length between the transformer with the buildings as user load, interference with electrical systems. This study aimed to analyze the voltage drop calculation, over load and power losses and balance the load on the Lancang Kuning University.
Results of analysis and calculation of electrical systems Lancang Kuning University gained power loss total of 23.5 kW and low voltage three phase occurred in the law school of 237, 5 volts and load imbalance of the phase R = 199.15 Amper ; Amper phase S = 154.05; and phase T = 121.6 Amper
Keywords: electrical system, power losses, voltage drop
Results of analysis and calculation of electrical systems Lancang Kuning University gained power loss total of 23.5 kW and low voltage three phase occurred in the law school of 237, 5 volts and load imbalance of the phase R = 199.15 Amper ; Amper phase S = 154.05; and phase T = 121.6 Amper
Keywords: electrical system, power losses, voltage drop
Full Text:
PDFReferences
Kadir Abdul, 2000, “ Transformator ”, PT. Elex Komputindo Kelompok Gramedia Jakarta.
Kadir Abdul, 2000, “ Distribusi dan Utilasi “, Universitas Indonesia.
Marsudi, Djiteng, 2006, “ Operasi Sistem Tenaga Listrik “, Yogjakarta : Graha Ilmu.
Muhaimin, 2000, “ Bahan – bahan Listrik “ , PT. Pradya Paramita.
Stevenson, William Jr. D, 1983., “ Analisa Sistem Tenaga Listrik “, Edisi Ke – 4, Penerbit Erlangga,
Jakarta.
Eris Meilandri, 2012, “ Analisa Aliran Daya Optimal Pada Sistem Kelistrikan Bali “, Vol 11, No 1,
JURNAL TEKNOLOGI ELEKTRO, Bali.
Suyono, 2011, “ Tingkat Keandalan Utilitas Kelistrikan Bangunan Gedung Bertingkat Di Kota
Semarang “, ISSN 1979-7451, Media Elektrika, Vol. 4 No. 1, Semarang.
Soebagio, 2012, “ Transformator “, ITS press, Surabaya.
Refbacks
- There are currently no refbacks.
FAKULTAS SAINS DAN TEKNOLOGI
UIN SUSKA RIAU
Kampus Raja Ali Haji
Gedung Fakultas Sains & Teknologi UIN Suska Riau
Jl.H.R.Soebrantas No.155 KM 18 Simpang Baru Panam, Pekanbaru 28293
Email: sntiki@uin-suska.ac.id