Reliability Improvement Using Sectionalizer with Section Technique Method

liliana liliana, Zulfatri Aini, Hanif Naufal Qasthari

Abstract


Unreliability in the 20 kV distribution system at PT. PLN (Persero) Rayon Rumbai feeder Rusa is more caused by disturbances that occur. During 2020 this feeder was recorded to experience the highest disturbance of 83 times, causing the system to experience frequent blackouts. This study seeks to identify and improve the reliability of the system in the feeder. The reliability of the system can be calculated and analyzed in more detail with the Section Tehnique method. This method can identify reliability by breaking the system into several sections so that the reliability of each section can be known. The increase in reliability is done by adding a sectionalizer to a system that has low reliability, there are two scenarios that are carried out in placing this sectionalizer correctly to produce better reliability. The results of the calculation of the reliability of each section of the system using the Section Technique method have been obtained, the average value of each reliability index is SAIFI 11.231 (f/customer.yr), SAIDI 30.55 (hr/customer.yr), CAIDI 11.015 (hr/customer interruption). ). The results of this index calculation do not meet the standards of SPLN 68-2 1986 with SAIFI 3.2 (f/customer.yr) and SAIDI 21.9 (hr/customer.yr). The reliability improvement was carried out by implementing sectionilizer on the feeder and the reliability index was obtained with SAIFI values 9.8185 (f/customer.yr), SAIDI 27.5292 (hr/customer.yr) and CAIDI 11.223 (hr/customer interruption) with an increase in SAIFI percentage. by 10.4%, SAIDI 8.8% and CAIDI 0.37%. With the addition of a sectionilizer, it is very helpful in increasing reliability, although it still does not meet the expected standard values.Unreliability in the 20 kV distribution system at PT. PLN (Persero) Rayon Rumbai feeder Rusa is more caused by disturbances that occur. During 2020 this feeder was recorded to experience the highest disturbance of 83 times, causing the system to experience frequent blackouts. This study seeks to identify and improve the reliability of the system in the feeder. The reliability of the system can be calculated and analyzed in more detail with the Section Tehnique method. This method can identify reliability by breaking the system into several sections so that the reliability of each section can be known. The increase in reliability is done by adding a sectionalizer to a system that has low reliability, there are two scenarios that are carried out in placing this sectionalizer correctly to produce better reliability. The results of the calculation of the reliability of each section of the system using the Section Technique method have been obtained, the average value of each reliability index is SAIFI 11.231 (f/customer.yr), SAIDI 30.55 (hr/customer.yr), CAIDI 11.015 (hr/customer interruption). ). The results of this index calculation do not meet the standards of SPLN 68-2 1986 with SAIFI 3.2 (f/customer.yr) and SAIDI 21.9 (hr/customer.yr). The reliability improvement was carried out by implementing sectionilizer on the feeder and the reliability index was obtained with SAIFI values 9.8185 (f/customer.yr), SAIDI 27.5292 (hr/customer.yr) and CAIDI 11.223 (hr/customer interruption) with an increase in SAIFI percentage. by 10.4%, SAIDI 8.8% and CAIDI 0.37%. With the addition of a sectionilizer, it is very helpful in increasing reliability, although it still does not meet the expected standard values.

Full Text:

PDF

References


C. A. Craig, “Electricity Generation, Electricity Consumption, and Energy Efficiency in the United States: A Dual Climatic-Behavioral Approach,” p. 164.

“Rahman et al. - 2017 - Energy Consumption Analysis Based on Energy Effici.pdf.”

M. F. Adiguna, “Pada Penyulang Kayutangi Menggunakan Metode Reliability Network Equivalent Approach ( RNEA ),” pp. 1–9, 2019.

A. T. Maliky, “Analisis Keandalan Sistem Distribusi 20 kV Pada Penyulang Pejangkungan Di PT PLN Pasuruan Menggunakan Metode RIA ( Reliability Index Assesment ),” pp. 835–843, 2015.

J. E. Wicaksono, “Penyulang Lowokwaru Menggunakan Metode RIA ( Reliability Index Assessment ) Dan Software Etap ( Electrical Transient Analisys Program ),” Universitas Muhammadiyah Malang, 2019.

M. Imron, “Inilah Daftar Kabupaten dan Kota Terbesar di Provinsi Riau Indonesia,” 2018. https://www.kuwaluhan.com/2018/08/inilah-daftar- kabupaten-dan-kota_27.html (accessed Sep. 24, 2020).

PT. PLN (Persero) ULP Rumbai, Rekap Bulanan Gangguan Feeder 2019. Pekanbaru, 2019.

(BPS) Badan Pusat Statistik, “Badan Pusat StatistiK Kependudukan Wilayah Rumbai,” Rumbai, 2019.

A. Triyollinna, R. Thayib, and A. Hamdadi, “Studi Penempatan Sectionalizer Pada Jaringan Distribusi 20 kV Di Penyulang Kelingi Untuk Meningkatkan Keandalan,” Mikrotiga, vol. 2, no. 1, pp. 5–10, 2015.

M. Fauzi, Irfan, “Analisis Koordinasi Recloser Dan Sectionalizer Pada Jaringan Distribusi 20 kV Di Gardu Induk Wonogiri,” 2019.

M. Sanaky, Rizal, “Peningkatan Indeks Keandalan Dengan Penambahan Recloser Pada Sistem Distribusi di PLTD Subaim Menggunakan Metode Section Technique,” Fakultas Teknologi Industri Institut Teknologi Nasional Malang, 2017.


Refbacks

  • There are currently no refbacks.


FAKULTAS SAINS DAN TEKNOLOGI
UIN SUSKA RIAU

Kampus Raja Ali Haji
Gedung Fakultas Sains & Teknologi UIN Suska Riau
Jl.H.R.Soebrantas No.155 KM 18 Simpang Baru Panam, Pekanbaru 28293
Email: sntiki@uin-suska.ac.id